Abstract
The problem of the optimal siting and placement of static compensates (STATCOMs) in
power systems is addressed in this paper from an exact mathematical optimization point of view. A
mixed-integer nonlinear programming model to present the problem was developed with the aim
of minimizing the annual operating costs of the power system, which is the sum of the costs of the
energy losses and of the installation of the STATCOMs. The optimization model has constraints
regarding the active and reactive power balance equations and those associated with the devices’
capabilities, among others. To characterize the electrical behavior of the power system, different
load profiles such as residential, industrial, and commercial are considered for a period of 24 h of
operation. The solution of the proposed model is reached with the general algebraic modeling system
optimization package. The numerical results indicate the positive effect of the dynamic reactive
power injections in the power systems on annual operating cost reduction. A Pareto front was built
to present the multi-objective behavior of the studied problem when compared to investment and
operative costs. The complete numerical validations are made in the IEEE 24-, IEEE 33-, and IEEE
69-bus systems, respectively.